Voltage Drop Calculator
Enter amps, volts and the one-way length. You get the voltage drop in volts and percent, the voltage at the load, and the smallest copper or aluminum wire that meets your drop target and the NEC ampacity. DC, single-phase and three-phase. Free, no signup.
Enter amps, volts and length
- Voltage drop
- Voltage drop (%)
- Voltage at load
- Ampacity
- Max breaker
- Smallest wire for 3 %
- Max length at 3 %
Uses the K method: K = 12.9 for copper and 21.2 for aluminum (ohm-circular mils per foot at about 75 °C, consistent with NEC Chapter 9 Table 8). Ampacity per NEC Table 310.16 (2017–2023 values; 30 °C ambient, no more than three current-carrying conductors, no correction or adjustment). The 3 % / 5 % figures come from NEC informational notes and are not requirements, but local codes may make them mandatory. AC results ignore reactance and power factor, which matters most on wire larger than 1/0. For PV circuits, enter the NEC 690.8 current. Not an engineering calculation — check with your local code and inspector. NEC® and National Electrical Code® are registered trademarks of NFPA; this site is not affiliated with NFPA.
Voltage drop formula
The calculator uses the K method. K = 12.9 for copper and 21.2 for aluminum (ohm-circular mils per foot at about 75 °C, consistent with NEC Chapter 9 Table 8). CM is the area of the wire in circular mils. AC results ignore reactance and power factor, which matters most on wire larger than 1/0.
Single-phase and DC: VD = 2 × K × I × L ÷ CM
Three-phase: VD = 1.732 × K × I × L ÷ CM
Voltage drop (%) = VD ÷ V × 100
I is the load current in amps and L is the one-way length in feet. With parallel sets, divide by the number of sets as well.
Example: a 44 A load at 240 V, single-phase, 160 ft away on 6 AWG copper (26,240 circular mils). The drop is 6.92 V, or 2.88 %, so the load sees 233.08 V. A 100 A three-phase load at 208 V, 80 ft away on 1 AWG aluminum, drops 3.51 V (1.69 %).
How much voltage drop is allowed
The NEC's 3 % for a branch circuit and 5 % for the feeder and branch circuit combined are informational notes to 210.19 and 215.2, not requirements (90.5(C)). Some rules do make a limit mandatory. Article 647, for sensitive electronic equipment, allows 1.5 % on the branch circuit and 2.5 % combined (647.4(D)). California's Title 24 energy code, §130.5(c), limits the feeder and branch circuit combined to 5 %. Check what your local code and inspector expect.
Single-phase, three-phase and DC
For DC and single-phase AC the current flows out and back, so the formula uses 2 × the one-way length. For three-phase the factor is √3 (1.732), and you enter the line-to-line voltage: 208, 240 or 480 V. Low-voltage DC runs lose a lot in percent: 20 A at 12 V over 25 ft on 10 AWG copper drops 1.24 V, which is 10.36 % of the supply.
Ampacity and the 240.4(D) limit
A wire that passes voltage drop can still be too small for the current. The calculator checks the ampacity from NEC Table 310.16 at 60 °C or 75 °C, and the small-conductor limit from 240.4(D): 15 A for 14 AWG copper, 20 A for 12 AWG copper, 30 A for 10 AWG copper, 15 A for 12 AWG aluminum and 25 A for 10 AWG aluminum. For example, 12 AWG copper is rated 25 A at 75 °C, but 240.4(D) still limits it to a 20 A breaker. For continuous loads the check uses 125 % of the current. The exceptions in 240.4(G), such as motor and air-conditioning circuits, are not included. To pick a size from scratch, use the wire size calculator.
More tools
Questions
How do you calculate voltage drop?
Multiply 2 × K × current × one-way length and divide by the wire area in circular mils. K = 12.9 for copper and 21.2 for aluminum (ohm-circular mils per foot at about 75 °C, consistent with NEC Chapter 9 Table 8). For 44 A at 240 V over 160 ft of 6 AWG copper that gives 6.92 V, or 2.88 %.
What is the maximum voltage drop allowed by the NEC?
The NEC's 3 % for a branch circuit and 5 % combined are informational notes, not requirements. Mandatory limits exist: Article 647 sensitive electronic equipment allows 1.5 % on the branch and 2.5 % combined (647.4(D)), and California Title 24 §130.5(c) limits the feeder and branch combined to 5 %. Your local code may add its own.
Does voltage drop depend on wire size?
Yes. The drop is inversely proportional to the wire area: double the circular mils and the drop is cut in half. On the 12 V example above, 10 AWG drops 10.36 % while 4 AWG keeps it under 3 %.
How do I calculate voltage drop for three-phase?
Use 1.732 (√3) instead of 2 and enter the line-to-line voltage. A 100 A load at 208 V three-phase, 80 ft away on 1 AWG aluminum, drops 3.51 V, which is 1.69 %.